The distribution components of the 71 Series have basically the same structure as those of the 71 Series.
They offer the following features:
• 4- or 5-pair organization • Contact wire Ø from 0.4 to 0.8 mm
• 3-point protection can be plugged in from the rear IDC contacts accessible when protection is plugged in Application Options The classic area of application of the 71 Series distribution system is the main distribution frame.
IDC Element:
Contact principle acc. to DIN IEC 352 :
Insulation displacement connection for the accomodation of one wire per IDC terminal
Spring material: Special brass
Contact force : > 10 N (0.4 mm conductor diameter)
Contact surface: Ag (4 to 7 µm)
Suitable for: Solid conductor with a diameter of 0.32 - 0.63 mm;
Outside diameter of max. 1.2 mm (with PE or PVC insulation)
Service life : > 200 clampings
Volume resistance at clamping point < 3 mohms (when new) acc. to DIN IEC 512-2:
Measured voltage > 20 mV, measured current 100 mA
Resistance change during the service life: < 5 mohms (based on new)
Dielectric strength : > 1500 V ~
Current carrying capacity : > 2.5 A at Tu 20°C
> 1.6 A at Tu 65°C
Insulation resistance under lab. conditions : > 1012 ohms (when new)
acc. to DIN IEC 512-2: after damp storage > 1010 ohms
Coupling capacitance : < 5 pF
Surge voltage acc. to VDE 0433, Table 3 Surge discharge 1.2/50 µs : > 1.5 kV
Noise voltage during vibration 5g /10 to 500 Hz, 20 clampings in series : < 0.4 mV
Module body: Polycarbonate
Utilization category acc. to DIN IEC 68: Max cold -25°C,
Dry heat +100°C
Humidity (constant) 21 days